(2) Manual Gain Switching
Manual gain switching uses G-SEL of OPTION field to switch between gain setting 1 and gain setting 2.
Type
Command Name
Input
G-SEL of OPTION field
(3) Automatic Gain Switching
Automatic gain switching is enabled only in position control. The switching conditions are specified using the
following settings.
Parameter Setting
Pn139
n.2
Select one of the following settings for switching condition A.
Parameter
n.0
[Factory setting]
n.1
n.2
Pn139
n.3
n.4
n.5
Automatic switching pattern 1 (Pn139.0 = 2)
Gain
Settings 1
Pn100
Pn101
Pn102
Pn121
Pn401
Setting
0
Switches to gain setting 1.
1
Switches to gain setting 2.
Switching Condition
Condition A satisfied.
Gain setting 1 to
gain setting 2
Condition A not satis-
Gain setting 2 to
fied.
gain setting 1
Switching Condition A
for Position Control
Positioning completed
Fixed in gain setting 1
signal (/COIN) ON
Positioning completed
Fixed in gain setting 2
signal (/COIN) OFF
Positioning near signal
Fixed in gain setting 1
(/NEAR) ON
Positioning near signal
Fixed in gain setting 2
(/NEAR) OFF
No output for position
reference filter and posi-
Fixed in gain setting 1
tion reference input OFF
Position reference input
Fixed in gain setting 2
ON
Switching Waiting Time 1 Pn135
Condition A
Switching Time 1 Pn131
satisfied
Switching Waiting Time 2 Pn136
Switching Time 2 Pn132
5.6 Additional Adjustment Function
Meaning
Switching Wait
Setting
Time
Pn135
Gain Switching
Waiting Time 1
Pn136
Gain Switching
Waiting Time 2
For Other than
When
Position Control
Enabled
(No Switching)
Immediately
Settings 2
Pn104
Pn105
Pn106
Pn122
Pn412
Condition A
not satisfied
Switching Time
Pn131
Gain Switching
Time 1
Pn132
Gain Switching
Time 2
Classification
Tuning
Gain
5-37
5