765-4501/0100-0000

4.2 Connections

4.2.1 Power supply

The product is powered through the X31 connection (Power in). Two supply cables can
be connected to the plug:
• Supply cable 1: 1L+ (U
• Supply cable 2: 2L+ (U
Both supply cables are electrically isolated from each other and functional ground.
Each pin of plug X31 (Power in) is connected to the same pin of socket X32 (Power out)
and makes it possible to pass the power on to the next device.
Supply Voltage In-
put
M12, L-coded, plug,
5-pin (4 + FE)
Note
Upper limit on current consumption from X32 (Power out)
Before connecting one or more products to the power supply on socket X32 (Power out),
read section
maximum permitted current consumption.

4.2.2 Communication Interfaces

4.2.2.1 IO-Link (Master)

IO-Link (Class A)
M12, A-coded,
socket, 5-pin
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
) and reference potential 1L−
1L
) and reference potential 2L−
2L
Supply Voltage
Pin
Output
1
2
3
4
FE
M12, L-coded,
socket, 5-pin (4 +
FE)
8 Power Supply Examples
Pin
Signal
1
1L+
2
DIO B (DI B/
DQ B)
3
1L–
4
C/Q
DIO A (DI A/
DQ A)
5
n. c.
Signal
Description
1L+
24 VDC supply voltage U
and sensor/actuator
2L−
Reference potential for 2L
1L−
Reference potential for 1L
2L+
24 VDC auxiliary/control voltage U
FE
Functional ground
[} 61]. There you will find information on the
Description
24 VDC supply voltage U
for sensor/actu-
1L
ator
Digital input/output channel B
Reference potential for 1L+
IO-Link data or
digital input/output channel A
Not connected
Properties
Table 4: Supply voltage
for system
1L
2L
Table 5: IO-Link (class A)
Wire Color
Brown
White
Blue
Black
-
17