3 Operation
3-8-2

Limiting Displayed Parameters

You can change the content of display on the LCD operator according to your purpose.
To know which parameters are changed, you can check by setting [UA-10] to 03.
If you do not want to display parameters for functions not in use, you can reduce them by setting
[UA-10] to 01.
Related Parameter
Item
Display restriction
selection
2nd-motor parameter
display selection
Option parameter dis-
play selection
User parameter
selection
I you are not using the input terminal function [SET] for switching to the second setting, by setting
[UA-21] to 00, you can reduce a great number of displayed items.
I you are not using option unit, by setting [UA-22] to 00, you can reduce indications for option unit.
3 - 34
Parameter
Data
[UA-10]
00
All parameters are displayed.
01
Parameters are displayed by function. Disabled functions are
not displayed with some exceptions.
02
Display is performed in accordance with the settings config-
ured by the user. Parameters set to [UA-31] to [UA-62] are dis-
played with some exceptions.
03
Parameters that have been changed from the factory default
settings and some other parameters are displayed.
04
Monitor parameters and some other parameters are dis-
played.
[UA-21]
00
Hides parameters of second setting [**2**].
01
Displays parameters of second setting [**2**].
[UA-22]
00
Hides parameters that start with o.
01
Displays parameters that start with o.
[UA-31] to
no
No assignment
[UA-62]
*****
Choose the code you want to display.
(all codes are subjected)
High-function General-purpose Inverter RX2 Series User's Manual
Description