8 Applied Settings
The inverter shuts off the output and, after the contactor release delay time passes, the control signal
039[CON] is turned off. (10)
The operation varies depending on whether the contactor check signal 107[COK] is set to the input ter-
minal function. (11)
With [COK] setting
Without [COK] setting
8-4-6

Forced Operation

Forced Operation Mode
In this mode, the motor runs at a fixed speed without interrupting the output of the inverter.
Set the [PA-01] forced operation to enabled 01 and turn on the [EMF] emergency forced operation
terminal (input terminal: 105) to enter the forced operation mode.
The command for the forced operation mode is set to [PA-02] the forced operation frequency setting
and [PA-03] the forced operation rotation direction command.
Precautions for Correct Use
• Once the forced operation mode is turned on, the inverter keeps operating until the power is
off.
• When using the forced operation mode, make sure that the system is safe if the operation
continues.
• Enabling the overcurrent retry, overvoltage retry, undervoltage retry or instantaneous power
failure retry requires a separate setting.
• After the [EMF] emergency forced operation terminal (input terminal: 105) is turned on, the
input terminal function except for the following are disabled.
[COK]: Contactor check signal
 Parameter Setting
Item
Mode selection for
Emergency-force drive
Frequency reference
setting at Emer-
gency-force drive
Direction command at
Emergency-force drive
 Input Terminal Setting
Item
Selecting the input ter-
minal
8 - 94
If the 107[COK] is not turned off during the contactor check time, the inverter trips with
the [E110] contactor error.
The inverter still does nothing.
Parameter
Data
00
[PA-01]
01
0.00 to
[PA-02]
590.00(Hz)
00
[PA-03]
01
Parameter
Data
[CA-01] to
105
[CA-11]
High-function General-purpose Inverter RX2 Series User's Manual
Description
Disabled
Enabled
Set the frequency command in the forced
operation mode.
Forward rotation command
Reverse rotation command
Description
[EMF] emergency forced operation terminal.
OFF: Disabled
ON: Forced operation mode (when [PA-01] = 01)
Default
data
00
0.00
00