Codes that
can be
Code
changed
during
operation
Window comparator for [Ai3]
CE-48
○
hysteresis width
Operation level at [Ai1] discon-
CE-50
○
nection
Operation level selection at [Ai1]
CE-51
○
disconnection
Operation level at [Ai2] discon-
CE-52
○
nection
Operation level selection at [Ai2]
CE-53
○
disconnection
Operation level at [Ai3] discon-
CE-54
○
nection
Operation level selection at [Ai3]
CE-55
○
disconnection
Low current signal output mode
CE201
○
selection, 2nd-motor
Low current detection level 1,
CE202
○
2nd-motor
Low current detection level 2,
CE203
○
2nd-motor
Over current signal output mode
CE205
○
selection, 2nd-motor
Over current detection level 1,
CE206
○
2nd-motor
Over current detection level 2,
CE207
○
2nd-motor
Over torque level (Forward driv-
CE220
○
ing), 2nd-motor
Over torque level (Reverse
CE221
○
regenerative), 2nd-motor
Over torque level (Reverse driv-
CE222
○
ing), 2nd-motor
Over torque level (Forward
CE223
○
regenerative), 2nd motor
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A,V). When the data of
[CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
High-function General-purpose Inverter RX2 Series User's Manual
Name
0 to 10 (%)
0 to 100 (%)
00 (Disabled)/01 (Enabled: out of range)
02 (Enabled: within the range)
0 to 100(%)
00 (Disabled)/01 (Enabled: out of range)/
02 (Enabled: within the range)
-100 to 100(%)
00 (Disabled)/01 (Enabled: out of range)/
02 (Enabled: within the range)
00 (During acceleration/deceleration, at constant
speed)/
01 (Only at constant speed)
(0.0 to 2.0)
× Inverter rated current
(0.0 to 2.0)
× Inverter rated current
00 (During acceleration/deceleration, at constant
speed)/
01 (Only at constant speed)
(0.0 to 2.0)
× Inverter rated current
(0.0 to 2.0)
× Inverter rated current
0.0 to 500.0 (%)
0.0 to 500.0 (%)
0.0 to 500.0 (%)
0.0 to 500.0 (%)
Appendices C Table of Parameters
Data range
*1
*1
*1
*1
Initial value
Note
0
0
00
0
00
0
00
01
1.0
× Inverter rated
current
1.0
× Inverter rated
current
01
1.0
× Inverter rated
current
1.0
C
× Inverter rated
current
100.0
100.0
100.0
100.0
C - 55