8 Applied Settings
Precautions for Correct Use
• The maximum input pulse in the phase coefficient monitoring mode becomes a maximum of
32 kpps. (When the duty ratio is approximately 50%)
• An accumulation counter value cannot be stored. After the power supply is turned on, the
value becomes zero.
• The maximum input pulse in the terminal input monitoring mode depends on the settings of
the input terminal response functions [CA-41] to [CA-51].
 Parameter
Item
Input terminal function
Output terminal func-
tion
Pulse train detection
object selection
Mode selection of
pulse train input
Comparing match out-
put ON-level for Pulse
count
Comparing match out-
put OFF-level for
Pulse count
Comparing match out-
put Maximum value for
Pulse count
Pulse counter monitor
Terminal Input Monitoring Mode
Monitors whether the input terminal functions [PLA] and [PLB] are turned on.
Normal rotation
pulse string input
Reverse rotation
pulse string input
Number of detected pulses
8 - 168
Parameter
Data
103
[CA-01] to
104
[CA-11]
097
[CC-01] to
091
[CC-07]
00
01
[CA-90]
02
03
00
[CA-91]
01
02
[CA-97]
0 to 65535
[CA-98]
0 to 65535
[CA-99]
0 to 65535
0 to
[dA-28]
2147483647
Terminal
[PLA]
Terminal
[PLB]
High-function General-purpose Inverter RX2 Series User's Manual
Description
[PLA]: Accepts a pulse input.
[PLB]: Accepts a pulse input.
[PCC]: Clears the integrated value.
[PCMP]: Outputs pulse compare-match sig-
nals.
Disabled
Frequency command
Speed feedback
Pulse count
90° phase difference
forward/reverse rotation command and rota-
tion direction
forward/reverse rotation pulse string
When the number of pulses reaches this set
value, Turn on [PCMP].
When the number of pulses reaches this set
value, Turn off [PCMP].
A one-shot pulse can be achieved when the
value is 0.
When the number of pulses reaches the set
value, the internal counter is cleared.
Displays the counter integrated value.
Default
data
-
-
00
00
0
0
0
-