The following is an example of operation of automatic resetting.
(Ex.1) When [bb-10]=01
Output frequency
Operation
instruction [FW]
*1
Error output
(Ex.2) When [bb-10]=02
Output frequency
Operation
instruction [FW]
*1
Error output
*1. When [bb-11]=00, the error output becomes the "[AL] output."
 Parameter
Item
Automatic reset
selection
Alarm signal selection
at Automatic error
reset is active
Automatic error reset
wait time
Automatic error reset
number
High-function General-purpose Inverter RX2 Series User's Manual
Restarting in accordance with [bb-41]
[bb -12]
Restarting in accordance with [bb-41]
[bb -12]
Parameter
Data
00
01
[bb-10]
02
00
[bb-11]
01
[bb-12]
0 to 600(s)
[bb-13]
0 to 10 (times)
Description
Invalid
Resetting starts when the operation instruc-
tion is turned off.
Resetting starts after the set time has
elapsed.
Outputting is available.
Outputting is not available.
Sets a stand-by time from when resetting
starts to when actual resetting starts.
Sets the number of automatic resetting.
8 Applied Settings
Default
data
00
00
2
3
8 - 171
8