8-11-5 Analog Output Terminal Switch Settings

With Analog output terminals Ao1 and Ao2, you can select voltage output or current output by operating
Switches SW3 and SW4 on the substrate.
Precautions for Correct Use
• In the switch setting on the substrate during factory setting, [A01] is output voltage; [A02] is
output current.
• Operate the switches on the substrate while the inverter power supply is turned off.
• When [Cd-10]=01 is set, [FM], [Ao1], and [Ao2] respectively perform outputs in accordance
with values of [Cd-15], [Cd-25], and [Cd-35].
 Parameter
Item
[Ao1] monitor output
selection
[Ao2] monitor output
selection
Analog monitor adjust
mode enable
Filter time constant of
[Ao1] monitor
[Ao1] Data type
selection
[Ao1] monitor bias
adjustment
[Ao1] monitor gain
adjustment
Output level setting at
[Ao1] monitor adjust
mode
Filter time constant of
[Ao2] monitor
[Ao2] Data type
selection
[Ao2] monitor bias
adjustment
[Ao2] monitor gain
adjustment
Output level setting at
[Ao2] monitor adjust
mode
High-function General-purpose Inverter RX2 Series User's Manual
Parameter
Data
Parameter
[Cd-04]
number for
8-11-4 Analog
Output Termi-
[Cd-05]
nal Adjustment
on page 8-178.
00
[Cd-10]
01
[Cd-21]
1 to 500[ms]
00
[Cd-22]
01
-100.0 to
[Cd-23]
100.0[%]
-1000.0 to
[Cd-24]
1000.0[%]
-100.0 to
[Cd-25]
100.0[%]
[Cd-31]
1 to 500[ms]
00
[Cd-32]
01
-100.0 to
[Cd-33]
100.0[%]
-1000.0 to
[Cd-34]
1000.0[%]
-100.0 to
[Cd-35]
100.0[%]
Description
Sets a parameter number.
Invalid.
Valid. Outputs to terminals output levels in
the adjustment mode.
Filters and outputs the selected data.
Outputs the absolute value of data.
Outputs data with a symbol as is.
Biases data to adjust Point 0 of data.
Apply a gain to data to adjust an inclination
in data.
Sets output in the adjustment mode. It
selects the maximum output (at 100.0%),
the minimum output (at 0.0%) ([Cd-22]=00),
or the minimum output (at -100.0%)
([Cd-22]=01).
Filters and outputs the selected data.
Outputs the absolute value of data.
Outputs data with a symbol as is.
Biases data to adjust Point 0 of data.
Apply a gain to data to adjust an inclination
in data.
Sets output in the adjustment mode. It
selects the maximum output (at 100.0%),
the minimum output (at 0.0%) ([Cd-32]=00),
or the minimum output (at -100.0%)
([Cd-32]=01).
8 Applied Settings
Default
data
[dA-01]
[dA-01]
00
100
00
0.0
100.0
100.0
100
0
20.0
80.0
100.0
8 - 181
8