8 Applied Settings
 Parameter
Item
The number of retries
after instantaneous
power failure
Selection of restart
mode @Instanta-
neous power failure/
under-voltage trip
Allowable under-volt-
age power failure time
Retry wait time before
motor restart
Instantaneous power
failure/under-voltage
trip alarm enable
(Ex.1) When [bb-20] = 00, tripping occurs
Control Power Supply
Inverter
Output
Motor Speed
Output signal
[AL]
(Ex.2) When [bb-20] ≠00 and [bb-24] = 00, it restarts at 0 Hz.
Control Power Supply
Inverter
Output
Motor Speed
Output signal
[AL]
Note The motor will trip after instantaneous power failure allowable time.
8 - 56
Parameter
Data
0 to 16/ ∞(255)
[bb-20]
(Counts)
00
01
02
[bb-24]
03
04
[bb-25]
0.3 to 25.0(s)
[bb-26]
0.3 to 100.0(s)
00
[bb-27]
01
02
IP error occurs
Free Running
Instantaneous power
failure allowable time
Free Running
Retry Standby
Time
High-function General-purpose Inverter RX2 Series User's Manual
Description
Sets the retry counts in case of instanta-
neous power failure.
If this is set to 0, the motor will trip upon
recovery from instantaneous power failure.
Restarts at 0 Hz
Restarts with the frequency matching
Restarts upon frequency pull-in
Detection speed (frequency) <v2.00 or
higher>
Trips after decelerating and stopping with
the frequency matching
Restarts if the instantaneous power failure
time is within the set value.
Starts after waiting for the set time upon
power voltage recovery.
Disabled
Enabled
Disabled during stop and deceleration stop
Default
data
0
01
1.0
0.3
00