6 Basic Parameter Settings
6-7-2

Switch Acceleration Time and Deceleration Time in Two Stages

Setting this function allows you to change the acceleration or deceleration time while driving in
response to the terminal command, the frequency command, or the direction command.
When [AC115] = 00, setting 031 [2CH] in any of the [CA-01] to [CA-11] and turning OFF/ON the target
Input terminal allows you to switch the acceleration or deceleration time.  (Example 1)
When [AC115] = 01, the frequency command and the relationship between the set values [AC116] and
[AC117] can be used to switch the acceleration or deceleration time.
 (Example 2)
When you set Select method to switch to Accel2/Decel2 Profile, 1st-motor [AC115] to 02 (Switching
normal/reverse rotation), the acceleration time and deceleration time can be configured by setting for-
ward or backward rotation.
 (Example 3)
Precautions for Correct Use
When the input terminal is used for switching, operation should be performed by assigning 031
[2CH] to any of [CA-01] to [CA-11].
 Parameter
Item
Maximum frequency
Acceleration time set-
ting 1, 1st-motor
Deceleration time set-
ting 1, 1st-motor
Acceleration time set-
ting 2, 1st-motor
Deceleration time set-
ting 2, 1st-motor
Select method to
switch to
Accel2/Decel2 Profile,
1st-motor
Accel1 to Accel2 Fre-
quency transition
point, 1st-motor
Decel1 to Decel2 Fre-
quency transition
point, 1st-motor
6 - 58
Parameters
Data
For IM,
[Hb105]
10.00 to
For SM
590.00(Hz)
(PMM),
[Hd105]
0.00 to
[AC120]
3600.00(s)
0.00 to
[AC122]
3600.00(s)
0.00 to
[AC124]
3600.00(s)
0.00 to
[AC126]
3600.00(s)
00
01
[AC115]
02
0.00 to
[AC116]
590.00(Hz)
0.00 to
[AC117]
590.00(Hz)
High-function General-purpose Inverter RX2 Series User's Manual
Description
Set the maximum value for the frequency.
Set, as the acceleration time, the time that it
takes to rise from 0 Hz to the maximum fre-
quency.
Set, as the deceleration time, the time that it
takes to fall from the maximum frequency to 0
Hz.
Set, as the acceleration time, the time that it
takes to rise from 0 Hz to the maximum fre-
quency.
Set, as the deceleration time, the time that it
takes to fall from the maximum frequency to 0
Hz.
Switching by [2CH] terminal (Example 1)
Switching by 2-stage acceleration or decelera-
tion frequency (Example 2)
Enabled only when the revolution is switched
between the forward and the backward direc-
tions (Example 3)
Enabled when 2-stage acceleration or decelera-
tion selection [AC115] is 01.
Enabled when 2-stage acceleration or decelera-
tion selection [AC115] is 01.
Default
data
*1
50
30.00
30.00
15.00
15.00
00
0.00
0.00

Hide quick links: