Set Frequency Matched Signal (Fa3/Fa5) - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

8 Applied Settings
8-8-3

Set Frequency Matched Signal (FA3/FA5)

FA3 outputs signals when the output frequency during acceleration/deceleration reaches the value of
Arrival Frequency Setting During Acceleration/Deceleration 1 (CE-10, CE-11).
FA5 outputs signals when the output frequency during acceleration/deceleration reaches the value of
Arrival Frequency Setting During Acceleration/Deceleration 2 (CE-12, CE-13).
Assign the output terminal functions 004 [FA3] and 006 [FA5] set frequency only output signals to one
of [CC-01] to [CC-07] that corresponds to the output terminal and output the signals.
The signals [FA3] and [FA5] can be output individually.
Precautions for Correct Use
• The operation of [FA3] can be set through [CE-10] and [CE-11].
• The operation of [FA5] can be set through [CE-12] and [CE-13].
[CE-10]/[CE-12]
Output
fon
Frequency
ON
[FA3]/[FA5]
OFF
 Parameter
Item
Output terminal func-
tion selection
Relay output terminal
function selection
Relay output terminal
function selection
Arrival frequency set-
ting during accelera-
tion 1
Arrival frequency set-
ting during decelera-
tion 1
Arrival frequency set-
ting during accelera-
tion 2
Arrival frequency set-
ting during decelera-
tion 2
8 - 146
fon
foff
Parameter
Data
[CC-01] to
[CC-05]
[CC-06]
004
006
[CC-07]
0.00 to
[CE-10]
590.00(Hz)
0.00 to
[CE-11]
590.00(Hz)
0.00 to
[CE-12]
590.00(Hz)
0.00 to
[CE-13]
590.00(Hz)
High-function General-purpose Inverter RX2 Series User's Manual
fon: 1% of the maximum frequency
foff: 2% of the maximum frequency
[CE-11]/[CE-13]
(Operation example)
foff
Maximum frequency: 60 Hz
When [CE-10] = [CE-11] = 50 Hz
fon=60×0.01=0.6Hz
• foff=60×0.02=1.2Hz
• In acceleration: On at 50 - 0.6 = 49.4 Hz
• In deceleration: On at 50 + 0.6 = 50.6 Hz
Description
[FA3]: The set frequency only reaching sig-
nal will be output to the output terminal
assigned.
[FA5]: The set frequency only reaching sig-
nal 2 will be output to the output terminal
assigned.
The frequency to judge that the frequency
has been reached in acceleration and output
the signal [FA3].
The frequency to judge that the frequency
has been reached in deceleration and out-
put the signal [FA3].
The frequency to judge that the frequency
has been reached in acceleration and output
the signal [FA5].
The frequency to judge that the frequency
has been reached in deceleration and out-
put the signal [FA5].
Off at 50 + 1.2 = 51.2 Hz
Off at 50 - 1.2 = 48.8 Hz
Default
data
-
0.00
0.00
0.00
0.00