4 Test Run
3
Operation command source selection [AA111]
When the operation command source is set to "02: LCD operator", "oFW" will be shown on the
LCD operator at the bottom in the area for displaying function of RUN key.
Note When the operation command source is set to reverse, "oRN" is displayed.
STOP
Output Frequency
AA111
First operation command selection
02: RUN key on operator keypad
Menu
4
Setting the electronic thermal level of motor [bC110]
Set the level so that it does not exceed the rated current of motor.
Precautions for Correct Use
Note that the motor may be burned if the electronic thermal level is not appropriately set.
Note
The electronic thermal for protecting the inverter works automatically.
STOP
Output Frequency
bC110
First electronic thermal level
Menu
4 - 6
H03
M1
0.00 Hz
Option
60.00Hz
oFW
H03
M1
0.00 Hz
25.0 A
[0.0-75.0]
Option
60.00Hz
oFW
High-function General-purpose Inverter RX2 Series User's Manual