Checking Retry Information - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

Checking Trip History
You can look through the history with the arrow Enter keys.
STOP
Trip history
Total count 20 times
1. E007 16/07/15 10:10
2. E001 16/07/15 08:55
3. E001 16/07/15 08:52
4. E009 16/07/12 10:10
5. E012 16/07/10 22:52
Menu
oFW
Trip history
Total count 20 times
6. E001 16/05/10 19:22
7. E001 16/04/21 20:59
8. E007 16/03/30 23:55
9. E001 15/12/25 01:34
10. E005 15/12/24 22:10

12-1-2 Checking Retry Information

The last 10 retry histories are displayed.
The latest retry history is displayed on the retry monitor 1.
The following data items are displayed on the monitor:
(a) Error factor for retry
(b) Output frequency (Hz) at retry
(c) Output current (A) at retry
(d) Main circuit DC voltage (V) at retry
(e) Operation state at retry
(f) Cumulative inverter operating time (h) before retry
(g) Cumulative inverter power-on time (h) before retry
Precautions for Correct Use
• While a retry is underway, the inverter tries to continue running. For a trip after a retry, the trip
information is recorded on the trip history.
• The information of the moment of error occurrence may not be fetched properly if the inverter
is forcibly turned OFF by its hardware.
• For a momentary overcurrent event, the current may be recorded in a value lower than the
actual value.
• To display time in retry history, you need to configure clock settings.
• To use the clock function, you need an optional battery that is separately sold (CR2032, 3V).
See 3-1-5 How to Set Battery and the Time Setting on page 3-12 for details.
High-function General-purpose Inverter RX2 Series User's Manual
H06
M1
46.49Hz
Details
Trip history details (No.10)
Motor overload error
E005 15/12/24
Output frequency : 0.50Hz
Output current
DC voltage
Status 1
Trip history details (No.10)
Motor overload error
22:10
Status 3
Status 4
: 49.71A
Status 5
: 274.1Vdc
RUN time
: Run
ON time
12 Troubleshooting
: Speed control
: Overload limit
: ----
: 20256 hr
: 27248 hr
12 - 3
12

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents