7 Advanced Settings
• Edge mode: [AF107]=00
[AF106] DC braking time setting is given priority, and the inverter performs DC braking (servo-lock
control) for the time set for [AF106]. After the operation command is turned off, if the output frequency
falls below [AF103] DC braking frequency, DC braking will be applied for the time set for [AF106].
Even if the operation command is turned on during DC braking, DC braking continues until the time
set for [AF106] elapses. (Ex.1), (Ex.2)
• Level mode: [AF107]=01
Operation commands are given priority. The inverter ignores [AF106] DC braking time and transits to
the normal operation. If the start command is turned on during DC braking, the inverter ignores the
time set for [AF106] and returns to the normal operation. (Ex.3), (Ex.4)
Edge mode: [AF107]=00
(Ex.1) When stopped ([AF104]≠0.00)
Operation
command FW
Output
frequency
[AF103]
(Ex.2) When stopped ([AF104]=0.00)
Operation
command FW
Output
frequency
7 - 92
ON
ON
Free-running
DC braking
[AF104]
[AF106]
ON
ON
DC braking
[AF106]
[AF103]
Level mode: [AF107]=01
(Ex.3) When stopped ([AF104]≠0.00)
Operation
ON
command FW
Output
frequency
[AF103]
(Ex.4) When stopped ([AF104]=0.00)
Operation
ON
command FW
Output
frequency
[AF103]
High-function General-purpose Inverter RX2 Series User's Manual
ON
Free-running
DC braking
[AF104]
[AF106]
ON
DC braking
[AF106]