Gain Adjustment of Analog Output
Terminal
Ao1
Ao2
You can change an inclination as shown in the below figure.
(V):(mA)
10 :20
5:10
0:0
0
-5: -10
(Ex.) Outputting information on the output current monitor to [Ao2] in a current range from 4 to 20 mA
Monitor the current in a range from 0 A to the inverter rated current.
[Cd-33]=20.0%, [Cd-34]=160.0%
(mA)
20
10
4
0
0A
Rated current
[Cd-33 ]= 20.0 (%)
(Ex.) Outputting information on the output torque monitor to [Ao2] in a voltage range from 0 to 10 V
Set a voltage output range from 0 to 10 V in a torque range from -200 to 200%.
[Cd-32]=01, [Cd-33]=50.0%, [Cd-34]=50.0%
(-) rated torque
(V)
10
0
-10
(-) rated torque × 2
Note When [Cd-32]=00 is set in the above described example, corresponding values in a range from 5 to 10 V
will be output for a range from 0 to -200% on the "(-) rated torque" side.
High-function General-purpose Inverter RX2 Series User's Manual
Common to voltage/current
Common to voltage/current
[Gain]=100.0(%)
[Gain]=200.0(%)
Change in
inclination
Outputting will
be made in this
range.
Maximum
Full scale (FS)
[Gain]=-50.0(%)
[Cd-34 ]=16 0.0 (%)
Output current (A)
Rated current × 2
(+) rated torque
[Cd-34 ]= 50.0%
Outputting will
be made in this
range.
Output torque (Nm)
0
[Cd-33 ]= 50.0%
(+) rated torque × 2
Current/voltage
[Gain]=50.0(%)
8 Applied Settings
Gain parameter
[Cd-24]
[Cd-34]
8
8 - 183