Precautions for Correct Use
• For using the bypass mode, it is necessary to implement a interlock taking into consideration
the operation delay of the contactor when shifting to the commercial operation. •Make sure
that the system operation is safe in using the mode.
• The timing of the contactor control can be taken using the [EMBP] bypass mode signal (out-
put terminal: 076) as the contactor control signal. Take a interlock between the contactor on
the commercial power supply side and that on the inverter output side.
• Since the commercial circuit does not operate either when the earth leakage circuit breaker
(ELCB) trips, connect the commercial circuit of another system to MC2 if the backup is
required.
NFB
ELCB
Sample connection diagram when shifting to the commercial operation and timing
Example of timing from INV to the commercial operation
Inverter output
EMBP
MC1
MC3
MC2
 Parameter Setting
Item
Commercial power
supply bypass function
selection
Delay time of Bypass
function
High-function General-purpose Inverter RX2 Series User's Manual
MC2
MC1
U
R
S
V
T
W
R0
T0
H
Ai1(10V)
L
AL0
AL1
FW
FW
AL2
RV
RV
16a
16c
COM
Operation
ON
ON
Interlock time for MC2 and MC3
(0.5 to 1 s)
ON
ON
Parameter
Data
00
[PA-04]
01
[PA-05]
0.0 to 1000.0(s)
THR
MC3
M
EMBP
To the contactor control
circuit
Description
Disabled
Enabled
Set the delay time until the bypass mode
operation.
8 Applied Settings
Default
data
00
5.0
8 - 97
8