Encoder Feedback Control - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

Phenomenon
The motor speed fol-
lows the command
slowly.
The motor operates
unstably.
Overshoot and/or
hunting occur.
The motor speed oscil-
lates gently.
Stabilization of the
operation requires a
long time.
It takes time for the
command value and
the motor speed to be
equal to each other.
Precautions for Correct Use
• When the revolution of the motor is hindered by such causes as the braking or the motor lock
caused by foreign objects, such hindrance may cause over current, or the like. When no such
adjustment as ones mentioned above improves the state, checking the portion around the
motor may sometimes improves it.
• If an application of load results in a great amount of change in the inverter's output frequency
monitor [dA-01], a function to automatically change the frequencies for the overload limiting
function, the momentary-stop non-stop function, the over voltage suppression function may
work depending upon the settings of the functions.

7-2-16 Encoder Feedback Control

In 3G3RX2 series, input of feedback from a motor into a control circuit terminal block of the main body
or into a PG option unit allows the control with sensor and the absolute position control.
Precautions for Correct Use
• When [CA-90] ≠ 00, Input terminals [A] and [B] of the main body are switched to the terminals
for feedback control.
• When [CA-90] = 02, the control with sensor and the absolute position control are possible
with Input terminals [A] and [B].
• When [CA-90] ≠ 02, the control with sensor and the absolute position control are possible
with terminals [EAP], [EBP], [EAN], and [EBN] of the PG option unit.
• To conduct the pulse train position control, terminals [SAP], [SBP], [SAN], and [SBN] of the
PG option unit are used.
• When the PG option unit was once set in a slot and was removed later, a trip occurs with a
feedback option connection error [E112].
• Trips are triggered by an encoder disconnection error [E100] by setting switches on the PG
option unit. For more details, see 2-3-6 Wiring for PG Option Unit on page 2-63.
High-function General-purpose Inverter RX2 Series User's Manual
Estimated cause(s)
Response of the out-
put is slow and the
Increment the proportional (P) gain [Hb170].
change in the fed-back
value is slow.
Response to the
fed-back value is too
Decrement the proportional (P) gain [Hb170].
quick.
Response to the inte-
Increment the integral (I) gain [Hb171].
gral operation is slow.
Response of the out-
put is slow and the
Decrement the integral (I) gain [Hb171].
change in the fed-back
value is slow.
Estimated cause(s)Exemplar measures to be taken
7 Advanced Settings
7 - 37
7