Omron RX2 Series User Manual page 605

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

Write to Holding Register [06 hex]
Writes data to the specified holding register.
Example
To write 50 Hz to the inverter with slave address as the 1st Base Frequency value.
Because the holding register 2F4E hex for the Multispeed-0 setting, 1st-motor (Ab110) has a data reso-
lution of 0.01 Hz, to set 50 Hz, set the written data to 5000 (1388 hex).
Query
No.
1
2
3
4
5
6
7
8
*1. During a broadcast, no response will be sent back.
*2. Note that the register start number is 2F4D hex, which is 1 less than the register number 2F4E hex.
Response
No.
1
2
3
4
5
6
7
8
Note that, except for FA-01, changing the parameter value on the data display does not update the dis-
played data realtime.
To view the updated value, once return to the parameter display and then display the data again.
If the Write to Holding Register function is executed normally, refer to Exception Response on page
9-18.
High-function General-purpose Inverter RX2 Series User's Manual
Field Name
*1
Slave address
Function code
Register starting number (high)
Register starting number (low)
Data to be changed (high)
Data to be changed (low)
CRC-16 (high)
CRC-16 (low)
Field Name
Slave address
Function code
Register starting number (high)
Register starting number (low)
Data to be changed (high)
Data to be changed (low)
CRC-16 (high)
CRC-16 (low)
9 Communications Functions
*2
*2
Example (hex)
01
06
2F
4D
13
88
1C
5F
Example (hex)
01
06
2F
4D
13
88
1C
5F
9 - 13