PID gain is time for PID1 gain to switch [AH-67] and switches continuously.
Each gain selected for PIDs can be checked by respective monitors [db-61] to [db-63].
Input signal [PRO]
Gain 2
Gain 1
8-1-3

PID Soft-start Function

In the case of using this function, enable PID control and set 01 to the [AH-75] PID soft-start function
selection.
It will move to PID control automatically after the elapse of the time set in [AH-80].
It accelerates to soft-start target level [AH-76] after start of soft-start.
Soft-start
target level [AH-76]
PID operation
 Parameter
Item
PID soft start function
enable
PID soft start target
level
Acceleration time set-
ting for PID soft start
function
PID soft start time
High-function General-purpose Inverter RX2 Series User's Manual
ON
[AH-67]
Output Frequency
Acceleration according to [AH-78]
Soft-start time [AH-80]
Parameter
Data
00
[AH-75]
01
0.00 to
[AH-76]
100.00(%)
0.00 to
[AH-78]
3600.00(s)
0.00 to
[AH-80]
600.00(s)
[AH-67]
ON
Description
Disable
Enable
It is a target value of the soft-start range with
the maximum frequency as 100%.
Sets acceleration time at the time of
soft-start.
Is soft-start operation time.
8 Applied Settings
Time
Default
data
00
100
30.00
0.00
8 - 19