5 Monitor
5-8-2
Output Power Monitor
The output power monitor [dA-34] displays the current power output to the inverter.
The integrated output power monitor [dA-36] displays the integrated data of the power output to the
inverter.
Additional Information
• Display gain for Accumulation output power monitor [UA-15] mode, the displayed contents
can be converted with gain.
Value indicated on [dA-36] = "Calculated output power value (kWh)"/[UA-15]
([UA-15] can be set from 1. to 1000. by an unit.)
• Accumulation output power monitor clear [UA-14] to "01" and then determining it, you can
clear an integrated output power value.
• Also, if 40 (OKHC: clearing of integrated output power) has been assigned to one of the input
terminals, integrated input power value can be cleared via that terminal.
Parameter
Item
Output power monitor
Integrated output power
monitor
Accumulation output
power monitor clear
Display gain for
Accumulation output
power monitor
Input terminal function
5 - 16
Parameter
Data
[dA-34]
0.00 to 600.00 (kW)
[dA-36]
0.0 to 100000.0 (kWh)
00
[UA-14]
01
[UA-15]
1 to 1000
[CA-01] to
040
[CA-11]
High-function General-purpose Inverter RX2 Series User's Manual
Description
Displays the output power.
Displays the integrated value of output
power.
Disable
Clear
Displays a value obtained by multiply-
ing by gain.
[OKHC] Clearing of integrated output
power terminal