8 Applied Settings
 Input Terminal Function
Item
PID sleep start termi-
nal
PID sleep cancel ter-
minal
(Ex.1) [AH-85] sleep start: 01 (output low)
Sleep operation starts will start when the output frequency stays below the level of [AH-86] continuously
for the set time of [AH-87].
[AH-93] Sleep cancel: 01 (deviation amount)
Cancel operation will start when PID deviation stays over [AH-96] continuously for the set time of
[AH-95]. Deviation operates with either figure (±).
PID target value
Wake start deviation amount [AH-96]
Output Frequency
Sleep start level [AH-86]
(Ex.2) [AH-85] sleep start: 01 (output low)
Sleep operation will start when the output frequency stays below [AH-86] continuously for the set time
of [AH-87].
[AH-93] Sleep cancel: 02 (feedback low)
Cancel operation will start when feedback stays below [AH-94] continuously for the set time of [AH-95].
PID target value
Wake start level [AH-94]
Output frequency
Sleep start level [AH-86]
8 - 22
Terminal name
Data
[SLEP]
058
[WAKE]
059
Feedback value
Sleep operation time [AH-87]
Feedback value
Sleep operation time [AH-87]
High-function General-purpose Inverter RX2 Series User's Manual
Description
Starts the sleep function with the terminal when
[AH-85] = 02.
Cancels the sleep function with the terminal when
[AH-93] = 03.
Wake operation time [AH-95]
Wake operation time [AH-95]