Pid2/Pid3/Pid4 Control - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

8 Applied Settings
Sleep Function Disable Time
Minimum operation time from start to sleep [AH-91] and minimum retaining time of the sleep status
[AH-92] can be set.
PID sleep operation can prevent the operation of switching between the sleep status and operation sta-
tus frequently.
Feedback value
PID target value + boost amount
PID target value
Wake start level [AH-84]
Output frequency
Sleep start level [AH-86]
8-1-5

PID2/PID3/PID4 Control

PID1 to PID4 controls operate independently.
Switching PID1 to 4 by terminal enables the use for switching batch control, etc.
In PID2, selecting PID1 output to target value enables control in consideration of influences from the 2
systems.
8 - 24
[AH-90]
Before sleep Minimum
operation time
[AH-91]
Sleep
operation
time
[AH-87]
High-function General-purpose Inverter RX2 Series User's Manual
Wake operation
time
[AH-95]
Sleep status Minimum
retaining time
[AH-92]