Omron RX2 Series User Manual page 549

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

Item
Ai1/Ai2/Ai3 abnormal
condition analog oper-
ation level selection
Window Comparator Operation
Ai1/Ai2/Ai3 inputs
Max(100%)
Hysteresis width
[CE-42]/[CE-45]/
[CE-48]
Min(Ai1/Ai2:0%)
(Ai3 :-100%)
[WCAi1]/[WCAi2]/[WCAi3]
[Ai1Dc]/[Ai2Dc]/[Ai3Dc]
00
[CE-51]
[CE-53]
01
[CE-55]
02
In the window comparator function, the signal will be output when the input level is within the specified
range.
In the break detection function, the signal will be output when the input level is out of the specified
range.
The logical values of the output signals can be modified through [CC-11] to [CC-17].
Specify the analog operation level to maintain the output level when the analog input becomes the max-
imum value because of a short circuit or when the analog input becomes 0 V because of a break.
To prevent the signal from being output at power-on, specify the on delay times [CC-20], [CC-22],
[CC-24], [CC-26], [CC-28], [CC-30], and [CC-32] of the output terminals.
High-function General-purpose Inverter RX2 Series User's Manual
Parameter
Data
00
Ai1:[CE-51]
01
Ai2:[CE-53]
Ai3:[CE-55]
02
Analog input value
8 Applied Settings
Description
Disabled
When the enabled WC signal is in operation (within
the range)
When the enabled WC signal is out of operation
(beyond the range)
Window comparator
upper limit level
[CE-40]/[CE-43]/[CE-46]
Window comparator
lower limit level
[CE-41]/[CE-44]/[CE-47]
8 - 149