Omron RX2 Series User Manual page 287

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

 Parameter
Item
First electronic thermal
level
Electronic thermal
characteristic
selection, 1st-motor
*1. The inverter rated current is switched by the load type selection [Ub-03]. Even if [bC110] is set to be high,
[E001] excessive current error occurs when the current exceeds the excess current level.
*2. Default data when default data selection (UB-02) is set to 01.
Change of Electronic Thermal Characteristics
Optimal protection characteristics can be achieved with the deterioration of the cooling ability of the
motor at a low speed taken account of. ([bC111]=00)
Frequency-dependent characteristics can be set in the selection of the electronic thermal characteris-
tics. ([bC111]=02)
Precautions for Correct Use
• Autocooling motor needs to be used with reduced load (current) since the cooling function of
the autocooling fan becomes less effective when the motor rotation frequency decreases.
• The reduced torque characteristics are in accordance with the heat generation of the auto-
cooling motor.
 Parameter
Item
Electronic thermal
characteristic
selection, 1st-motor
*1. Default data when default data selection (UB-02) is set to 01.
High-function General-purpose Inverter RX2 Series User's Manual
Parameters
Data
In range of 20 to 300%
of the inverter rated
[bC110]
current (unit: A)
00
01
[bC111]
02
Parameters
Data
00
[bC111]
01
02
6 Basic Parameter Settings
Description
Sets the protection current of motor.
*1
Reduced torque characteristics:
Pattern for cooling function deteriora-
tion at a low speed
Constant torque characteristics:
Pattern for constant output
Free setting:
Multiple patterns are available
according to the motor characteris-
tics.
Description
Reduced torque characteristics:
Pattern for cooling function deterioration at a
low speed
Constant torque characteristics:
Pattern for constant output
Free setting:
Multiple patterns are available according to the
motor characteristics.
Default
data
1.00 ×
Inverter
rated
current
*2
01
6
Default
data
*1
01
6 - 49