7 Advanced Settings
Item
Selection of restart
mode @over-volt-
age
Wait time of restart
@over-voltage
Frequency Matching after Free-run Stop [FRS] Release [bb-40]=01
(Ex.) Frequency matching operation after free-run stop [FRS]
Operation
command FW
Free-running
stop FRS
Motor speed
[bb-42]
0
Item
Restart mode after
FRS release
Retry wait time
before motor
restart
Frequency Matching After Reset [RS] [bb-41]=01
(Ex.) Frequency matching operation after reset [RS]
Operation
command FW
Reset RS
Motor speed
[bb-42]
0
Item
Restart mode after
RS release
Retry wait time
before motor
restart
Note If the frequency matching after reset has been set, starting after power-on will also occur with frequency
matching.
7 - 68
Parameter
Data
[bb-30]
01
[bb-31]
0.3 to 100.0(s)
Free-running
[bb-26]
Restarting with frequency matching
Parameter
Data
[bb-40]
01
[bb-26]
0.3 to 100.0(s)
Free-running
[bb-26]
Restarting with frequency matching
Parameter
Data
[bb-41]
01
[bb-26]
0.3 to 100.0(s)
High-function General-purpose Inverter RX2 Series User's Manual
Description
Performs frequency matching restart.
Sets the wait time after the retry operation on
overvoltage.
Description
Performs frequency matching restart.
Sets the wait time after the free-run stop
release.
Description
Performs frequency matching restart.
Sets the wait time after the reset release.
Default
data
01
0.3
Default
data
00
0.3
Default
data
00
0.3

Hide quick links: