Overspeed Error Detection - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

8-3-9

Overspeed Error Detection

The over-speed error detection function judges that the speed is excessive if the feedback speed
exceeds the over-speed level.
This function operates when other than "0.0" is specified for [bb-80] Over-speed error detection level.
The overspeed is detected by the feedback frequencies displayed on [dA-08] speed detection monitor.
When the speed has exceeded [bb-80] Over-speed error detection level and [bb-81] Over-speed error
detection time has elapsed, it is judged as an over-speed error.
When an over-speed error occurs, the inverter trips with [E107] Over-speed error.
Precautions for Correct Use
To use this function, speed feedback by the encoder is required.
Speed
0
 Parameter
Item
Over speed detection
level
Over speed detection
time
Speed detection value
monitor
High-function General-purpose Inverter RX2 Series User's Manual
bb -81
bb -81
The inverter trips due to an over-speed error.
Parameter
Data
[bb-80]
0.0 to 150.0(%)
[bb-81]
0.0 to 5.0(s)
-590.00 to
[dA-08]
590.00(Hz)
bb -80
Description
Set the overspeed level at 100% to which
the maximum frequency is set.
Sets the time to judge the speed to be an
error after it has excessively increased. The
inverter trips with [E107] Over-speed error.
Displays the data obtained through encoder
feedback.
8 Applied Settings
Default
data
135.0
0.5
-
8 - 79
8

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents