6 Basic Parameter Settings
6-5
Limit Frequency and Operation Com-
mands
6-5-1

Limit Frequency and Operation Commands

A limiter of the upper and lower limits of the frequency command can be set. The upper limiter can be
set from analog input by setting [bA101].
This function limits a frequency command even if a frequency command value outside the range
between the upper and lower limiters is set.
Precautions for Correct Use
• The upper and lower limiters should be set lower than the maximum frequency. Otherwise,
warning of the inconsistency will arises.
• To set the limiters, set the upper limiter [bA102] first. Make sure that it is larger than the lower
limiter value [bA103].
• Under the restriction by the upper and lower limiters and the minimum frequency, a LIM icon
appears.
• To enable Upper Frequency limit [bA102], set [bA101] = 07: Parameter setting.
 Parameter
Item
Max. frequency
Minimum frequency
adjustment, 1st-motor
Frequency limit
selection, 1st-motor
Upper Frequency limit,
1st-motor
Lower Frequency limit,
1st-motor
Frequency upper limit
monitor
*1. Default data when default data selection (UB-02) is set to 01.
6 - 44
Parameters
Data
For IM
[Hb105]
10.00 to
For SM
590.00(Hz)
(PMM)
[Hd105]
0.00 to
[Hb130]
10.00(Hz)
[bA101]
00 to 13
0.00, lower
limiter of
[bA102]
frequency
-max. fre-
quency (Hz)
0.00, start
frequency
[bA103]
-upper lim-
iter of fre-
quency (Hz)
0.00 to
[dA-14]
590.00(Hz)
High-function General-purpose Inverter RX2 Series User's Manual
Description
Sets the max. frequency.
IM: Induction motor [AA121]=00-10
SM(PMM): Synchronous motor (permanent
magnet motor) [AA121]=11, 12
Sets the min. frequency to start output.
Disabled when [AA121]=09, 10.
00 (disabling)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/ 03 (Ai3 terminal input)/
04 (Reserved)/ 05 (Reserved)/06 (Reserved)/
07 (parameter setting)/08 (RS485)/
09 (option 1)/ 10 (option 2)/11 (option 3)/
12 (pulse string input (main body))/
13 (pulse string input (Option))
Sets the upper limit of the frequency command.
Sets the lower limit of the frequency command.
Disabled when 0.00 is set.
The employed upper limit of the frequency is
shown.
Default
data
*1
50
0.50
00
0.00
0.00
-