Omron RX2 Series User Manual page 770

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

12 Troubleshooting
E035 Thermistor Error
If an abnormal temperature is observed during detection of resistor level change in an external thermis-
tor, the inverter turns OFF its output. (When thermistor function is enabled.)
Occurrence
Motor is heated.
Motor is not heated.
E036 Brake Error
This error occurs when the inverter can not detect whether the brake check signal is ON or OFF during
waiting time after the inverter has output a brake releasing signal. (When brake function is enabled.)
Occurrence
Error occurred after
operation.
E038 Low-speed Range Overload Error
This error occurs to protect the main element if the inverter has output at a low frequency of 0.2 Hz or
below.
When such a low frequency is detected by the built-in electronic thermal function, the inverter turns
OFF its output.
Occurrence
Error occurred
during output at low
speed.
12 - 16
Estimated cause(s)
The motor hasn't been
The cooling environment needs to be improved.
cooled sufficiently.
Heavy load has been
The motor's driving environment needs to be re-examined.
applied for a long time.
Inadequate thermistor
Re-examination of the thermistor function setting may improve
function setting
the situation.
The thermistor is broken
The thermistor needs to be repaired.
down.
The situation may be improved by taking a noise countermea-
Malfunction due to noise
sure such as wiring separation.
Estimated cause(s)
Disconnection of signal
Check the wiring of brake check signal and whether the signal
line.
is ON or OFF.
The situation may be improved by re-examination of brake
Brake function setting
check waiting time or input terminal logics according to the
sequence of the signal.
Estimated cause(s)
Load at low-speed range needs to be reduced. If the error
The motor load is heavy.
occurs frequently, you need to select an inverter with a capac-
ity large enough for the motor.
High-function General-purpose Inverter RX2 Series User's Manual
Exemplar measures to be taken
Exemplar measures to be taken
Exemplar measures to be taken

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents