Function Mode; Group F: Basic Function Parameters - Omron MX2 Series User Manual

Multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

4-2

Function Mode

The table below lists the function mode parameters.
If the data exceeds the display digits, the Digital Operator displays the upper digits for monitoring and
the lower digits for setting. To monitor digits that are not displayed, use the digit shift display mode. For
details, refer to Digit Shift Display Mode on page 3-11.
4-2-1

Group F: Basic Function Parameters

Parameter
Function name
No.
Output Frequency
F001
Setting/Monitor
1st Acceleration
F002
Time 1
2nd Acceleration
F202
Time 1
1st Deceleration
F003
Time 1
2nd Deceleration
F203
Time 1
RUN Direction Selec-
F004
tion
*1. The digit shift display mode can be used.
*2. In high-frequency mode.
*3. Changing the direction during operation has the same effect as when giving a command in the opposite direc-
tion.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Monitor or data range
0.0, Starting Frequency to
1st/2nd Maximum Fre-
quency
When the PID function is
*1
enabled: 0.00 to 9999.00
*1
0.00 to 3600.00
*1
0.00 to 3600.00
*1
0.00 to 3600.00
*1
0.00 to 3600.00
00: Forward
01: Reverse
4 Parameter List
Changes
Default data
during
RUN
6.00
Enabled
*2
Enabled
10.00 (30.00)
*2
Enabled
10.00 (30.00)
*2
Enabled
10.00 (30.00)
*2
Enabled
10.00 (30.00)
*3
00
Enabled
Unit
Page
Hz
P. 5-23
%
4
s
s
P. 5-32
s
s
P. 5-21
4 - 5

Advertisement

Table of Contents
loading

Table of Contents