8 Applied Settings
(Ex.1-1) [Cb-07]=00
Maximum
frequency
[Cb-04]
[Cb-03]
0
[Cb-05]
[Cb-06]
(0V/0mA)
(Ex.1-2) [Cb-07]=00
Maximum
frequency
[Cb-03]
[Cb-04]
[Cb-05]
0
[Cb-06]
(0V/0mA)
Relation between Analog Input Ai2 and Frequency Command
The following table is a relation between Analog Input Ai2 and Frequency Command.
Item
Filter time constant of
Terminal [Ai2]
Start value of Terminal
[Ai2]
End value of Terminal
[Ai2]
Start rate of Terminal
[Ai2]
End rate of Terminal
[Ai2]
Start point selection of
Terminal [Ai2]
8 - 164
(Ex.2-1) [Cb-07]=01
The output frequency
for 0% to [Cb-05] is
[Cb-03].
Analog input
100
(10V/20mA)
(V/ mA)
(Ex.2-2) [Cb-07]=01
The output frequency
for [Cb-06] to 100% is
[Cb-04].
Analog input
100
(10V/20mA)
(V/ mA)
Parameter
Data
[Cb-11]
1 to 500(ms)
0.00
[Cb-13]
to 100.00(%)
0.00
[Cb-14]
to 100.00(%)
0.0
[Cb-15]
to [Cb-16](%)
[Cb-17]
[Cb-16]
to 100.0(%)
00
[Cb-17]
01
Maximum
frequency
[Cb-04]
[Cb-03]
[Cb-05]
[Cb-06]
0
(0V/0mA)
Maximum
frequency
[Cb-03]
[Cb-04]
0
[Cb-05]
[Cb-06]
(0V/0mA)
Description
Filters the input.
Sets a frequency instruction ratio when set-
ting a start ratio for analog input.
Sets a frequency instruction ratio when set-
ting an end ratio for analog input.
With respect to a minimum ratio for analog
input for 0 to 10 V/0 to 20 mA, sets a start
ratio.
With respect to an external frequency
instruction for 0 to 10 V, 0 to 20 mA, sets an
end ratio.
For an instruction for a value of one of
0.00% to the "Start amount [Cb-13]" and to
the "End amount [Cb-14]," whichever is
lower, one of the values of the "Start amount
[Cb-13]" and the "End amount [Cb-14],"
whichever is lower, is output.
For an instruction for a value of one of
0.00% to the "Start amount [Cb-13]" and to
the "End amount [Cb-14]," whichever is
lower, a value of 0.00% is output.
High-function General-purpose Inverter RX2 Series User's Manual
The output frequency
for 0% to [Cb-05] is 0
Hz.
Analog input
100
(10V/20mA)
(V/ mA)
The output frequency
for [Cb-06] to 100% is 0
Hz.
Analog input
100
(10V/20mA)
(V/ mA)
Default
data
16
0.00
100.00
20.0
100.0
01