8-6

Alarm Signal

8-6-1

Alarm Signal (AL)

If an overcurrent, overvoltage, or some other error occurs, the inverter shuts off its output and gener-
ates an alarm signal. This is called a "Trip".
A trip state can be canceled by resetting the inverter, by which the alarm signal also turns OFF.
To reset the inverter, press the STOP/RESET key or input the reset terminal. However, you may not be
able to reset some trip factors by using these methods. In such case, cycle the power supply.
The [AL] function is assigned in the initial state to the contact c relay [CC-07] of AL1-AL0 and AL2-AL0.
You can set the output specifications of contacts a and b to output terminals 11-15, relay output termi-
nals 16A-16C, AL1-AL0, and AL2-AL0 individually.
Precautions for Correct Use
When an inverter outputs error by an interruption of its power supply, in some cases, changes
of wirings and contact selections may alleviate this symptom.
Alarm Relay AL
The operations of AL1-AL0 and AL2-AL0 are as follows.
[CC-17]
00
01
The specifications of the relay contacts AL1-AL0 and AL2-AL0 are as follows.
AL1-AL0
AL2-AL0
High-function General-purpose Inverter RX2 Series User's Manual
Control power
Inverter error output
Abnormal
On
Normal
Off
Abnormal
On
Normal
Off
Maximum contact capacity
Minimum contact capacity
Maximum contact capacity
Minimum contact capacity
Output terminal state
AL1-AL0
Close
Open
-
Open
Open
Close
-
Open
Resistive load
AC250V,2A
DC30V,3A
AC100V,10mA
DC5V,100mA
AC250V,1A
DC30V,1A
AC100V,10mA
DC5V,100mA
8 Applied Settings
AL2-AL0
Open
Close
Close
Close
Open
Close
Inductive load
AC250V,0.2A
DC30V,0.6A
AC250V,0.2A
DC30V,0.2A
8 - 123
8