Class Specifications - Omron RX2 Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX2 Series:
Table of Contents

Advertisement

1-3-2
200V Class Specifications
3G3RX2-A2
A2004 A2007 A2015 A2022 A2037 A2055 A2075 A2110 A2150 A2185 A2220 A2300 A2370 A2450 A2550
VLD
Applicable motor
LD
(4-pole) capacity (kW)
ND
VLD
Rated output
LD
current (A)
ND
VLD
Overload
LD
current rating
ND
Output
Rated output voltage
VLD
200V
LD
Rated
ND
capacity
VLD
(kVA)
240V
LD
ND
VLD
Rated input
LD
current (A) *1
ND
Rated input AC
Input
voltage
Power supply
VLD
equipment
LD
capacity (kVA)
ND
*2
VLD
Carrier frequency
LD
operating range *3
ND
Motor start torque *4
Regenerative braking
Braking
Minimum resistance
that can be
connected (Ω)
Height (mm)
Dimension
Width (mm)
Depth (mm)
Protective construction
Approximate mass (kg)
*1. The rated input currents shown in the table are the values when the rated current is output. The values vary depending on impedance on the power supply
(wiring, breaker, input reactor option, etc.)
*2. The power supply equipment capacities shown in the table are the values when 220V rated current is output. The values vary depending on impedance on
the power supply (wiring, breaker, input reactor option, etc.)
*3. The setting of rated values for carrier frequencies [bb101]/[bb201] are internally limited in accordance with the description. Also, it is recommended to set
values equivalent to or above (maximum output frequency for driving ×10) Hz for the setting of carrier frequencies [bb101]/[bb201]. Also, in the case of
induction motor (IM) control, for items other than those subject to V/f control, it is recommended to set carrier frequency at 2kHz or more. In the case of
synchronous motor (SM)/permanent magnet motor (PMM) control, it is recommended to set carrier frequency at 8kHz or more.
*4. The value of the sensor-less vector control applied to the ND rating in the Standard motor. Torque characteristics may vary depending on the control
method and the motor used.
*5. Based on self declaration.
High-function General-purpose Inverter RX2 Series User's Manual
0.75
1.5
2.2
3.7
5.5
0.75
1.5
2.2
3.7
5.5
0.4
0.75
1.5
2.2
3.7
4.4
8.0
10.4
15.6
22.8
3.7
6.3
9.4
12.0
19.6
3.2
5.0
8.0
11.0
17.5
3-phase (3-wire) 200 to 240V (depending on receiving voltage)
1.5
2.8
3.6
5.4
7.9
1.3
2.2
3.3
4.2
6.8
1.1
1.7
2.8
3.8
6.1
1.8
3.3
4.3
6.5
9.5
1.5
2.6
3.9
5.0
8.1
1.3
2.1
3.3
4.6
7.3
5.2
9.5
12.4
18.6
27.1
4.4
7.5
11.2
14.3
23.3
3.8
6.0
9.5
13.1
20.8
Control power supply: Power supply single phase 200 to 240V/allowable variation range 170 to 264V,
50Hz (allowable variation range: 47.5 to 52.5Hz)/60Hz (allowable variation range: 57 to 63Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240V/allowable variation range 170 to 264V,
50Hz (allowable variation range: 47.5 to 52.5Hz)/60Hz (allowable variation range: 57 to 63Hz)
2.0
3.6
4.7
7.1
10.3
1.7
2.9
4.3
5.4
8.9
1.5
2.3
3.6
5.0
7.9
Equipped with BRD circuit (with a discharging resistor separately installed)
50
50
35
35
35
255
255
255
255
255
150
150
150
150
150
140
140
140
140
140
3
3
3
3
3
7.5
11
15
18.5
22
7.5
11
15
18.5
22
5.5
7.5
11
15
18.5
33.0
46.0
60.0
80.0
93.0
30.0
40.0
56.0
73.0
85.0
25.0
32.0
46.0
64.0
76.0
110% 60sec / 120% 3sec
120% 60sec / 150% 3sec
150% 60sec / 200% 3sec
11.4
15.9
20.8
27.7
32.2
10.4
13.9
19.4
25.3
29.4
8.7
11.1
15.9
22.2
26.3
13.7
19.1
24.9
33.3
38.7
12.5
16.6
23.3
30.3
35.3
10.4
13.3
19.1
26.6
31.6
39.3
54.8
71.4
95.2
110.7
35.7
47.6
66.7
86.9
101.2
29.8
38.1
54.8
76.2
90.5
15.0
20.9
27.2
36.3
42.2
13.6
18.1
25.4
33.1
38.6
11.3
14.5
20.9
29.0
34.5
0.5 to 10.0kHz
0.5 to 12.0kHz
0.5 to 16.0kHz
200%/0.3Hz
16
10
10
7.5
7.5
260
260
260
390
390
210
210
210
245
245
170
170
170
190
190
IP20*5 / UL open type
6
6
6
10
10
1 Overview
30
37
45
55
75
30
37
45
55
75
22
30
37
45
55
124
153
185
229
295
113
140
169
210
270
95.0
122
146
182
220
43.0
53.0
64.1
79.3
102.2
39.1
48.5
58.5
72.7
93.5
32.9
42.3
50.6
63.0
76.2
51.5
63.6
76.9
95.2
122.6
47.0
58.2
70.3
87.3
112.2
39.5
50.7
60.7
75.7
91.5
147.6
182.1
220.2
272.6
351.2
134.5
166.7
201.2
250.0
321.4
113.1
145.2
173.8
216.7
261.9
56.3
69.4
83.9
103.9
133.8
51.3
63.5
76.7
95.3
122.5
43.1
55.3
66.2
82.6
99.8
Regenerative braking unit
separately installed
5
---
---
---
---
390
540
550
550
700
245
300
390
390
480
190
195
250
250
250
10
22
33
33
47
1 - 11
1