Restart Overvoltage
In case of overvoltage, you can restart without causing tripping.
Precautions for Correct Use
If overvoltage continues to be observed, there are some possible causes: short deceleration
time, heavy load, motor operated by external force, etc.
 Parameter
Item
The number of retries
after over voltage
Selection of restart
mode @over-voltage
Wait time of restart
@over-voltage
(Ex.1) When [bb-23] = 00, tripping occurs
P-N Voltage
Inverter
Output
Motor Speed
Output signal
[AL]
(Ex.2) When [bb-23] ≠00 and [bb-30] = 00, it restarts at 0 Hz.
P-N Voltage
Inverter
Output
Motor Speed
Output signal
[AL]
High-function General-purpose Inverter RX2 Series User's Manual
Parameter
Data
[bb-23]
0 to 5 (Counts)
00
01
02
[bb-30]
03
04
[bb-31]
0.3 to 100.0(s)
Overvoltage Detection Level
Overvoltage error occurs
Free Running
Overvoltage Detection Level
Free Running
Retry Standby Time
Description
Sets the retry counts in case of overvoltage.
If this is set to 0, the motor will trip upon
overvoltage.
Restarts at 0 Hz
Restarts with the frequency matching
Restarts upon frequency pull-in
Detection speed (frequency) <v2.00 or
higher>
Trips after decelerating and stopping with
the frequency matching
Restarts after waiting for the set time upon
overvoltage.
8 Applied Settings
Default
data
0
01
0.3
8 - 61
8