Monitoring/Scaling Settings - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
DI3
DI4
DI5
DI6
Other [bit]
45.17
Tariff currency unit
Local currency
EUR
USD
45.18
CO2 conversion
factor
0.000...65.535
tn/MWh
45.19
Comparison power
0.00...10000000.00
kW
45.21
Energy calculations
reset
Done
Reset
46
46 Monitoring/scaling
settings
46.01
Speed scaling
0.10...30000.00
rpm
Description
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Source selection (see
Terms and abbreviations
Specifies the currency used for the savings calculations.
The currency is determined by the language selection (see
parameter
96.01
Language).
Euro.
US dollar.
Defines a factor for conversion of saved energy into CO
emissions (kg/kWh or tn/MWh).
Factor for conversion of saved energy into CO
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
Motor power.
Resets the savings counter parameters 45.01...45.10.
Reset not requested (normal operation), or reset complete.
Reset the savings counter parameters. The value reverts
automatically to Done.
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
Speed reference
ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.12 Maximum
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in eg.
fieldbus communication.
Acceleration/deceleration terminal/initial speed.
Parameters 279
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
on page 136). -
2
emissions.
2
23
speed).
Def/FbEq16
4
5
6
7
EUR
100
101
102
0.500
tn/MWh
1 = 1 tn/MWh
0.00 kW
1 = 1 kW
Done
0
1
1500.00 rpm
1 = 1 rpm