Fieldbus Adapter (Fba) - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

284 Parameters
No.
Name/Value
115.2 kbps
230.4 kbps
49.04
Communication
loss time
0.3...3000.0 s
49.05
Communication
loss action
No action
Fault
Last speed
Speed ref safe
49.06
Refresh settings
Done
Configure
50
50 Fieldbus adapter
(FBA)
50.01
FBA A enable
Disable
Enable
50.02
FBA A comm loss
func
No
Fault
Description
115.2 kbit/s.
230.4 kbit/s.
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
action
is taken.
Panel/PC tool communication timeout.
Selects how the drive reacts to a control panel (or PC tool)
communication break.
No action taken.
Drive trips on
7081 Control panel loss Programmable fault:
49.05 Communication loss
Drive generates an
A7EE Panel loss
speed to the level the drive was operating at. The speed is
determined on the basis of actual speed using 850 ms low-
pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Drive generates an
A7EE Panel loss
speed to the speed defined by parameter
safe
(or
28.41 Frequency ref safe
is being used).
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Applies the settings of parameters 49.01...49.05.
Note: Refreshing may cause a communication break, so
reconnecting the drive may be required.
Refresh done or not requested.
Refresh parameters 49.01...49.05. The value reverts
automatically to Done.
Fieldbus communication configuration.
See also chapter
Fieldbus control through a fieldbus adapter
(page 405).
Enables/disables communication between the drive and
fieldbus adapter A, and specifies the slot the adapter is
installed into.
Communication between drive and fieldbus adapter A
disabled.
Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 1.
Selects how the drive reacts upon a fieldbus communication
break. The time delay is defined by parameter
comm loss t
out.
No action taken.
Communication break detection active. Upon a
communication break, the drive trips on a
communication
fault and coasts to a stop.
49.05 Communication loss
action.
warning and freezes the
warning and sets the
22.41 Speed ref
when frequency reference
50.03 FBA A
7510 FBA A
Def/FbEq16
4
5
10.0 s
10 = 1 s
Fault
0
1
2
3
Done
0
1
Disable
0
1
No
0
1