ABB ACS580 Firmware Manual page 266

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

262 Parameters
No.
Name/Value
40.02
Process PID
feedback actual
-32768.00...
32767.00 PID
customer units
40.03
Process PID
setpoint actual
-32768.00...
32767.00 PID
customer units
40.04
Process PID
deviation actual
-32768.00...
32767.00 PID
customer units
40.06
Process PID status
word
Bit
Name
0
PID active
1
Setpoint frozen
2
Output frozen
3
PID sleep mode
4
Sleep boost
5
Reserved
6
Tracking mode
7
Output limit high
8
Output limit low
9
Reserved
10
PID set
11
Reserved
12
Internal setpoint
active
13...15 Reserved
0000h...FFFFh
40.07
Process PID
operation mode
Off
On
Description
Displays the value of process feedback after source
selection, mathematical function (parameter
feedback
function), and filtering. See the control chain
diagram on page 430.
This parameter is read-only.
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 431.
This parameter is read-only.
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 431.
This parameter is read-only.
PID deviation.
Displays status information on process PID control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID setpoint frozen.
1 = Process PID controller output frozen.
1 = Sleep mode active.
1 = Sleep boost active.
1 = Tracking function active.
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
1 = Internal setpoint active (see par. 40.16...40.16)
Process PID control status word.
Activates/deactivates process PID control.
Note: Process PID control is only available in external
control; see section
Local control vs. external control
86).
Process PID control inactive.
Process PID control active.
40.10 Set 1
(40.18 Set 1 setpoint
inversion. See the control
(page
Def/FbEq16
-
1 = 1 PID
customer unit
-
1 = 1 PID
customer unit
-
1 = 1 PID
customer unit
-
1 = 1
Off
0
1