No.
Name/Value
CMOD-01
CMOD-02
CHDI-01
15.03
DI status
0000h...FFFFh
15.04
RO/DO status
0000h...FFFFh
15.05
RO/DO force
selection
Bit
Value
0
1 = Force RO4 to value of bit 0 of parameter
1
1 = Force RO5 to value of bit 1 of parameter
2...4
Reserved
5
1 = Force DO1 to value of bit 5 of parameter
6...15
Reserved
0000h...FFFFh
15.06
RO/DO forced data
0000h...FFFFh
15.07
RO4 source
Not energized
Energized
Ready run
Enabled
Started
Magnetized
Running
Ready ref
Description
CMOD-01.
CMOD-02.
CHDI-01.
Displays the status of the digital inputs DI7...DI12 on the
extension module
Bit 0 indicates the status of DI7.
Example: 001001b = DI7 and DI10 are on, remainder are off.
This parameter is read-only.
Status of digital input/outputs.
Displays the status of the relay outputs RO4 and RO5 and
digital output DO1 on the extension module.
Bits 0...1 indicates the status of RO4...RO5; bit 5 indicates
the status of DO1.
Example: 100101b = RO4 is on, RO5 is off. and DO1 is on.
This parameter is read-only.
Status of relay/digital outputs.
The electrical statuses of the relay/digital outputs can be
overridden for eg. testing purposes. A bit in parameter
RO/DO forced data
is provided for each digital input, and its
value is applied whenever the corresponding bit in this
parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
15.05
and 15.06).
Override selection for relay/digital outputs.
Allows the data value of a forced relay or digital output to be
changed from 0 to 1. It is only possible to force an output that
has been selected in parameter
Bits 0...1 are the forced values for RO4...RO5; bit 5 is the
forced value for DO1.
Forced values of relay/digital outputs.
Selects a drive signal to be connected to relay output RO4.
Output is not energized.
Output is energized.
Bit 1 of
06.11 Main status word
Bit 0 of
06.16 Drive status word 1
Bit 5 of
06.16 Drive status word 1
Bit 1 of
06.17 Drive status word 2
Bit 6 of
06.16 Drive status word 1
Bit 2 of
06.11 Main status word
15.06
15.06 RO/DO forced
data.
15.06 RO/DO forced
data.
15.06 RO/DO forced
data.
15.05 RO/DO force
selection.
(see page 145).
(see page 146).
(see page 146).
(see page 147).
(see page 146).
(see page 145).
Parameters 167
Def/FbEq16
1
2
3
-
1 = 1
-
1 = 1
0000h
1 = 1
0000h
1 = 1
Not
energized
0
1
2
4
5
6
7
8

Hide quick links: