ABB ACS580 Firmware Manual page 228

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

224 Parameters
No.
Name/Value
30.02
Torque limit status
Bit
Name
0
Undervoltage
1
Overvoltage
2
Minimum torque *1 = Torque is being limited by
3
Maximum torque *1 = Torque is being limited by
4
Internal current
5
Load angle
6
Motor pullout
7
Reserved
8
Thermal
9
Max current
10
User current
11
Thermal IGBT
12...15 Reserved
*Only one out of bits 0...3, and one out of bits 9...11 can be on simultaneously. The bit typically
indicates the limit that is exceeded first.
0000h...FFFFh
30.11
Minimum speed
-30000.00...
30000.00 rpm
30.12
Maximum speed
-30000.00...
30000.00 rpm
30.13
Minimum frequency
-500.00...500.00
Hz
Description
Displays the torque controller limitation status word.
This parameter is read-only.
Description
*1 = Intermediate DC circuit undervoltage
*1 = Intermediate DC circuit overvoltage
motoring limit
or
30.27 Power generating limit
motoring limit
or
30.27 Power generating limit
1 = An inverter current limit (identified by bits 8...11) is active
(With permanent magnet motors and reluctance motors only)
1 = Load angle limit is active, ie. the motor cannot produce any more
torque
(With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot produce any more
torque
1 = Input current is being limited by the main circuit thermal limit
*1 = Maximum output current (I
*1 = Output current is being limited by
*1 = Output current is being limited by a calculated thermal current
value
Torque limitation status word.
Defines the minimum allowed speed.
WARNING! This value must not be higher than
Maximum
speed.
WARNING! In speed control mode only. In frequency
control mode, use frequency limits
Minimum allowed speed.
Defines the maximum allowed speed.
WARNING! This value must not be lower than
Minimum
speed.
WARNING! In speed control mode only. In frequency
control mode, use frequency limits
Maximum speed.
Defines the minimum allowed frequency.
WARNING! This value must not be higher than
Maximum
frequency.
WARNING! in frequency control mode only.
Minimum frequency.
30.19 Minimum torque
1,
30.20 Maximum torque
1,
) is being limited
MAX
30.17 Maximum current
30.12
(30.13
and 30.14).
30.11
(30.13
and 30.14).
30.14
Def/FbEq16
-
30.26 Power
30.26 Power
1 = 1
-1500.00 rpm
See par.
46.01
1500.00 rpm
See par.
46.01
-50.00 Hz
See par.
46.02