282 Parameters
No.
Name/Value
46.23
At torque hysteresis
0.0...300.0%
46.31
Above speed limit
0.00...30000.00
rpm
46.32
Above frequency
limit
0.00...1000.00 Hz
46.33
Above torque limit
0.0...1600.0%
46.41
kWh pulse scaling
0.001...
1000.000 kWh
47

47 Data storage

47.01
Data storage 1
real32
-2147483.000...
2147483.000
47.02
Data storage 2
real32
-2147483.000...
2147483.000
Description
Defines the "at setpoint" limits for torque control of the drive.
When the absolute difference between reference
Torque reference act
4) and actual torque
torque) is smaller than
46.23 At torque
considered to be "at setpoint". This is indicated by bit 8 of
06.11 Main status
word.
Drive at setpoint
(06.11
bit 8 = 1)
Limit for "at setpoint" indication in torque control.
Defines the trigger level for "above limit" indication in speed
control. When actual speed exceeds the limit, bit 10 of
Drive status word 2
is set.
"Above limit" indication trigger level for speed control.
Defines the trigger level for "above limit" indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
06.17 Drive status word 2
"Above limit" indication trigger level for frequency control.
Defines the trigger level for "above limit" indication in torque
control. When actual torque exceeds the limit, bit 10 of
Drive status word 2
is set.
"Above limit" indication trigger level for torque control.
Defines the trigger level for the "kWh pulse" on for 50 ms. The
output of the pulse is bit 9 of
"kWh pulse" on trigger level.
Data storage parameters that can be written to and read from
using other parameters' source and target settings.
Note that there are different storage parameters for different
data types.
See also section
Data storage parameters
Data storage parameter 1.
32-bit data.
Data storage parameter 2.
32-bit data.
(26.73
(01.10 Motor
hysteresis, the drive is
01.10
(%)
26.73
+
46.23
(%)
26.73
(%)
26.73
-
46.23
(%)
0%
is set.
05.22 Diagnostic word
3.
(page 133).
Def/FbEq16
5.0%
See par.
46.03
1500.00 rpm
06.17
See par.
46.01
50.00 Hz
See par.
46.02
300.0%
06.17
See par.
46.03
1.000 kWh
1 = 1 kWh
0.000
-
0.000
-