Embedded Fieldbus - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
58

58 Embedded fieldbus

58.01
Protocol enable
None
Modbus RTU
58.02
Protocol ID
58.03
Node address
0...255
58.04
Baud rate
4.8 kbps
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
76.8 kbps
115.2 kbps
58.05
Parity
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
58.06
Communication
control
Enabled
Refresh settings
Silent mode
Description
Configuration of the embedded fieldbus (EFB) interface.
See also chapter
Fieldbus control through the embedded
fieldbus interface (EFB)
Enables/disables the embedded fieldbus interface and
selects the protocol to use.
None (communication disabled).
Embedded fieldbus interface is enabled and uses the Modbus
RTU protocol.
Displays the protocol ID and revision.
This parameter is read-only.
Protocol ID and revision.
Defines the node address of the drive on the fieldbus link.
Values 1...247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Node address (values 1...247 are allowed).
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
4.8 kbit/s.
9.6 kbit/s.
19.2 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
76.8 kbit/s.
115.2 kbit/s.
Selects the type of parity bit and number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
Eight data bits, no parity bit, one stop bit.
Eight data bits, no parity bit, two stop bits.
Eight data bits, even parity bit, one stop bit.
Eight data bits, odd parity bit, one stop bit.
Takes changed EFB settings in use, or activates silent mode.
Normal operation.
Refreshes settings (parameters 58.01...58.05, 58.14...58.17,
58.25, 58.28...58.34) and takes changed EFB configuration
settings in use. Reverts automatically to Enabled.
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
settings
selection of this parameter.
(page 377).
settings).
settings).
settings).
Parameters 291
Def/FbEq16
None
0
1
-
1 = 1
1
58.06
1 = 1
19.2 kbps
58.06
1
2
3
4
5
6
7
8 EVEN 1
58.06
0
1
2
3
Enabled
0
1
2
Refresh