Refer to the motor nameplate for the following nominal value settings of the motor. Enter the
values exactly as shown on the motor nameplate.
Example of a nameplate of an induction (asynchronous) motor:
ABB Motors
3
motor
M2AA 200 MLA 4
IEC 200 M/L 55
Hz
kW
V
690 Y
30
50
400 D
50
30
660 Y
50
30
380 D
30
50
50
415 D
30
440 D
35
60
Cat. no
3GAA 202 001 - ADA
6312/C3
Select the motor type.
Check that the motor data is correct. Values are
predefined on the basis of the drive size but you
should verify that they correspond to the motor.
Start with the motor nominal current.
If you have to change the value, go to the edit
view of the selected row by pressing
this symbol is shown at the end of the row).
Set the correct value:
• Use
and
right.
• Use
and
Press
(Save) to accept the new setting, or
press
(Cancel) to go back to the previous
view without making changes.
Continue to check/edit the nominal values and
select scalar or vector control mode.
Motor nominal cos Φ and nominal torque are
optional.
Roll down with
After editing the last row, the panel goes to the
next view.
To go directly to the next view, press
No
Ins.cl. F
IP 55
IA/IN t E/s
r/min
A
cos
1475
32.5
0.83
1475
56
0.83
1470
34
0.83
1470
59
0.83
1475
54
0.83
1770
59
0.83
6210/C3
180
IEC 34-1
(when
to move the cursor left and
to change the value.
to see the last row in the view.
Start-up, control with I/O and ID run 17
(Next).

Hide quick links: