Pfc Configuration - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
71.23
Internal setpoint 3
71.26
Setpoint min
71.27
Setpoint max
71.31
Deviation inversion
71.32
Gain
71.33
Integration time
71.34
Derivation time
71.35
Derivation filter time
71.36
Output min
71.37
Output max
71.38
Output freeze
enable
71.39
Deadband range
0.0...32767.0
71.40
Deadband delay
0.0...3600.0 s
71.58
Increase prevention
71.59
Decrease
prevention
71.62
Internal setpoint
actual
76

76 PFC configuration

76.01
PFC status
Description
See parameter
40.23 Set 1 internal setpoint
See parameter
40.26 Set 1 setpoint
See parameter
40.27 Set 1 setpoint
See parameter
40.31 Set 1 deviation
See parameter
40.32 Set 1
See parameter
40.33 Set 1 integration
See parameter
40.34 Set 1 derivation
See parameter
40.35 Set 1 derivation filter
See parameter
40.36 Set 1 output
See parameter
40.37 Set 1 output
See parameter
40.38 Set 1 output freeze
The control program compares the absolute value of
parameter
71.04 Deviation act value
defined by this parameter. If the absolute value is within the
deadband range for the time period defined by parameter
71.40 Deadband
delay, PID's deadband mode is activated
and
71.06 PID status word
PID's output is frozen and
frozen
is set.
If the absolute value is equal or greater than the deadband
range, PID's deadband mode is deactivated.
Range
Defines the deadband delay for the deadband function. See
parameter
71.39 Deadband
Delay
See parameter
40.58 Set 1 increase
See parameter
40.59 Set 1 decrease
See parameter
40.62 PID internal setpoint
PFC (Pump and fan control) and Autochange configuration
parameters. See also section
page 114.
Displays the running/stopped status of the PFC motors.
PFC1, PFC2, PFC3 and PFC4 always correspond to the
1st...4th motor of the PFC system. If
auxiliary PFC
auxiliary PFC is set to
represents the motor connected to the drive and PFC2 the
first auxiliary motor (the 2nd motor of the system). If
set to
All
motors, PFC1 is the first motor, PFC2 the 2nd. The
drive can be connected to any of these motors depending on
the Autochange functionality.
3.
min.
max.
inversion.
gain.
time.
time.
time.
min.
max.
enable.
to the deadband range
bit 9
Deadband active
is set. Then
71.06 PID status word
bit 2
range.
prevention.
prevention.
actual.
Pump and fan control (PFC)
76.74 Autochange
Aux motors
only, PFC1
Parameters 299
Def/FbEq16
0.00 PID
customer
units
0.00
32767.00
Not inverted
(Ref - Fbk)
1.00
60.0 s
0.000 s
0.0 s
-32768.0
32767.0
Not selected
0.0
Output
1 = 1
0.0 s
1 = 1 s
No
No
-
on
-
76.74
is