ABB ACS580 Firmware Manual page 205

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
23.13
Deceleration time 1
0.000...1800.000 s
23.14
Acceleration time 2
0.000...1800.000 s
23.15
Deceleration time 2
0.000...1800.000 s
23.20
Acc time jogging
0.000...1800.000 s
23.21
Dec time jogging
0.000...1800.000 s
23.23
Emergency stop
time
0.000...1800.000 s
Description
Defines deceleration time 1 as the time required for the speed
to change from the speed defined by parameter
scaling
(not from parameter
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference.
If the reference changes faster than the set deceleration rate,
the motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits (or not to exceed a safe DC link voltage). If
there is any doubt about the deceleration time being too
short, ensure that DC overvoltage control is on (parameter
30.30 Overvoltage
control).
Note: If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
Deceleration time 1.
Defines acceleration time 2. See parameter
Acceleration time
1.
Acceleration time 2.
Defines deceleration time 2. See parameter
Deceleration time
1.
Deceleration time 2.
Defines the acceleration time for the jogging function ie. the
time required for the speed to change from zero to the speed
value defined by parameter
See section
Rush control
Acceleration time for jogging.
Defines the deceleration time for the jogging function ie. the
time required for the speed to change from the speed value
defined by parameter
46.01 Speed scaling
See section
Rush control
Deceleration time for jogging.
Defines the time inside which the drive is stopped if an
emergency stop Off3 is activated (ie. the time required for the
speed to change from the speed value defined by parameter
46.01 Speed scaling
or
Emergency stop mode and activation source are selected by
parameters
21.04 Emergency stop mode
Emergency stop source
also be activated through fieldbus.
Note:
• Emergency stop Off1 uses the standard deceleration ramp
as defined by parameters 23.11...23.15.
• The same parameter value is also used in frequency
control mode (ramp parameters 28.71...28.75).
Emergency stop Off3 deceleration time.
30.12 Maximum
speed) to zero.
23.12
23.13
46.01 Speed scaling.
(page 98).
to zero.
(page 98).
46.02 Frequency scaling
and
21.05
respectively. Emergency stop can
Parameters 201
Def/FbEq16
20.000 s
46.01 Speed
10 = 1 s
60.000 s
10 = 1 s
60.000 s
10 = 1 s
60.000 s
10 = 1 s
60.000 s
10 = 1 s
3.000 s
to zero).
10 = 1 s