374 Fault tracing
Code
Fault / Aux. code
(hex)
7510
FBA A communication
Programmable fault:
FBA A comm loss func
8001
ULC underload fault
8002
ULC overload fault
80A0
AI supervision
Programmable fault:
12.03 AI supervision
function
80B0
Signal supervision
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
80B1
Signal supervision
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
80B2
Signal supervision
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
80B3
Signal supervision
(Editable message text)
Programmable fault:
32.36 Supervision 4 action
80B4
Signal supervision
(Editable message text)
Programmable fault:
32.46 Supervision 5 action
80B5
Signal supervision
(Editable message text)
Programmable fault:
32.56 Supervision 6 action
9081
External fault 1
(Editable message text)
Programmable fault:
External event 1 source
31.02 External event 1
type
9082
External fault 2
(Editable message text)
Programmable fault:
External event 2 source
31.04 External event 2
type
Cause
Cyclical communication
between drive and fieldbus
50.02
adapter module A or between
PLC and fieldbus adapter
module A is lost.
User load curve: Signal has
been too long under the
underload curve.
User load curve: Signal has
been too long over the
overload curve.
An analog signal is outside the
limits specified for the analog
input.
Fault generated by the signal
supervision function 1.
Fault generated by the signal
supervision function 2.
Fault generated by the signal
supervision function 4.
Fault generated by the signal
supervision function 4.
Fault generated by the signal
supervision function 5.
Fault generated by the signal
supervision function66.
Fault in external device 1.
31.01
Fault in external device 2.
31.03
What to do
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
Fieldbus adapter
(FBA),
settings,
52 FBA A data in
data
out.
Check cable connections.
Check if communication master is able to
communicate.
See parameter
37.04 ULC underload
actions.
See parameter
37.03 ULC overload
actions.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
Standard
AI.
Check the source of the fault (parameter
32.07 Supervision 1
signal).
Check the source of the fault (parameter
32.17 Supervision 2
signal).
Check the source of the fault (parameter
32.27 Supervision 3
signal).
Check the source of the fault (parameter
32.37 Supervision 4
signal).
Check the source of the fault (parameter
32.47 Supervision 5
signal).
Check the source of the fault (parameter
32.57 Supervision 6
signal).
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
50
51 FBA A
and
53 FBA A
12
31.01
31.03