Terminal sizes:
R0...R3: 0.2...2.5 mm
0.14...1.5 mm
R5...R9: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes:
1
)
If DI3 and DI4 are both active or inactive, the frequency/speed reference is unchanged.
The existing frequency/speed reference is stored during stop and power down.
2)
In scalar control (default): See Menu - Primary settings - Start, stop, reference - Constant
frequencies or parameter
In vector control: See Menu - Primary settings - Start, stop, reference - Constant speeds
or parameter
22.26 Constant speed
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Note: Use shielded twisted-pair cables for digital signals.
Input signals
•
Start/Stop selection (DI1)
•
Direction selection (DI2)
•
Reference up (DI3)
•
Reference down (DI4)
•
Constant frequency/speed 1 (DI5)
•
Run enable (DI6)
Output signals
•
Analog output AO1: Output frequency
•
Analog output AO2: Motor current
•
Relay output 1: Ready run
•
Relay output 2: Running
•
Relay output 3: Fault (-1)
2
(terminals +24V, DGND, DCOM, B+, A-)
2
(terminals DI, AI, AO, AGND, RO, STO)
2
(all terminals)
28.26 Constant frequency
1.
Control macros 69
1.