408 Resistor braking
ACS580-01-...
099A-6
125A-6
144A-6
192A-6
242A-6
271A-6
Symbols
R min
= minimum allowed brake resistor that can be connected to the brake chopper
R max
= maximum allowed brake resistor that allows P BRmax
P BRmax
= maximum braking capacity of the drive, must exceed the desired braking power.
WARNING!
Do not use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are not
able to handle the overcurrent caused by the low resistance.

Parameter settings for external braking chopper and resistor

Disable the overvoltage control of the drive with parameter 30.30 Overvoltage
control.
Disable parameter 43.06 Braking chopper function as parameter group 43 Brake
chopper is used for internal braking chopper and resistor only.
For more information, see NBRA-6xx Braking Choppers Installation and start-up
guide (3AFY58920541 [English]) and ACS-BRK Brake Units Installation and start-up
guide (3AFY61514309 [English]).
R min
R max
ohm
ohm
4.3
11.5
4.3
8.5
3.2
7.0
2.2
5.8
2.2
4.8
2.2
4.0
P BRmax
Reference resistor types
kW
78
SAFUR80F500
107
SAFUR80F500
128
SAFUR80F500
157
SAFUR125F500
188
2xSAFUR200F500
228
2xSAFUR200F500