254 Parameters
No.
Name/Value
35.52
Zero speed load
50...150%
35.53
Break point
1.00...500.00 Hz
35.54
Motor nominal
temperature rise
Motor nominal
temperature rise
0...300 °C or
32...572 °F
Description
Defines the motor load curve together with parameters
Motor load curve
and
35.53 Break
maximum motor load at zero speed of the load curve. A
higher value can be used if the motor has an external motor
fan to boost the cooling. See the motor manufacturer's
recommendations.
See parameter
35.51 Motor load
Zero speed load for the motor load curve.
Defines the motor load curve together with parameters
Motor load curve
and
35.52 Zero speed
break point frequency of the load curve ie. the point at which
the motor load curve begins to decrease from the value of
parameter
35.51 Motor load curve
parameter
35.52 Zero speed
See parameter
35.51 Motor load
Break point for the motor load curve.
Defines the temperature rise of the motor above ambient
when the motor is loaded with nominal current. See the motor
manufacturer's recommendations.
The unit is selected by parameter
Temperature
Ambient temperature
Temperature rise.
point. Defines the
curve.
load. Defines the
towards the value of
load.
curve.
96.16 Unit
selection.
Def/FbEq16
35.51
100%
1 = 1%
35.51
45.00 Hz
See par.
46.02
80 °C or
176 °F
Time
1 = 1°