ABB ACS580 Firmware Manual page 161

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
12.11
AI1 actual value
0.000...20.000 mA
or 0.000...10.000 V
12.12
AI1 scaled value
-32768.000...
32767.000
12.13
AI1 forced value
0.000...20.000 mA
or 0.000...10.000 V
12.15
AI1 unit selection
V
mA
12.16
AI1 filter time
0.000...30.000 s
Description
Displays the value of analog input AI1 in mA or V (depending
on whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
Value of analog input AI1.
Displays the value of analog input AI1 after scaling. See
parameters
12.19 AI1 scaled at AI1 min
at AI1
max.
This parameter is read-only.
Scaled value of analog input AI1.
Forced value that can be used instead of the true reading of
the input. See parameter
Forced value of analog input AI1.
Selects the unit for readings and settings related to analog
input AI1.
Note: This setting must match the corresponding hardware
setting on the drive control unit. See chapter Electrical
installation, section Switches in the Hardware manual of the
drive and the default control connections for the macro in use
in chapter
Control macros
(either by cycling the power or through parameter
Control board
boot) is required to validate any changes in the
hardware settings.
Volts.
Milliamperes.
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
Filter time constant.
and
12.20 AI1 scaled
12.02 AI force
selection.
(page 59). Control board reboot
t
)
Parameters 157
Def/FbEq16
-
1000 = 1 unit
-
1 = 1
-
1000 = 1 unit
V
96.08
2
10
0.100 s
1000 = 1 s