Settings
• Menu - Backups
• Parameter
96.07 Parameter save manually

User parameter sets

The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets. To change a user parameter set, the drive has
to be stopped.
A user parameter set contains all editable values in parameter groups 10...99 except
• I/O extension module settings (group 15)
• data storage parameters (group 47)
• fieldbus communication settings (groups 50...53 and 58).
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, the motor ID run needs to
be performed with each motor and the results saved to different user sets. The
appropriate set can then be recalled when the motor is switched.
Settings
• Menu - Primary settings - Advanced functions - User sets
• Parameters
96.10...96.13

Data storage parameters

Twelve (eight 32-bit, four 16-bit) parameters are reserved for data storage. These
parameters are unconnected by default and can be used for linking, testing and
commissioning purposes. They can be written to and read from using other
parameters' source or target selections.
Settings
Parameter group
47 Data storage
(page 309).
(page 310).
(page 282).
Program features 133