ABB ACS580 Firmware Manual page 253

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
KTY83 analog I/O
1 × Pt1000 analog
I/O
2 × Pt1000 analog
I/O
3 × Pt1000 analog
I/O
Ni1000
Description
KTY83 sensor connected to the analog input selected by
parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
Pt1000 sensor connected to a standard analog input selected
by parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
As selection
1 × Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt1000 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
Ni1000 sensor connected to the analog input selected by
parameter
35.14 Temperature 1 AI source
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
and an analog
to
V
(volt).
AO, set the source
Temp sensor 1
and an analog
to
V
(volt).
AO, set the source
Temp sensor 1
I/O, but with two sensors
I/O, but with three sensors
and an analog
to
V
(volt).
AO, set the source
Temp sensor 1
Parameters 249
Def/FbEq16
12
13
14
15
16